Case study - Fuel depot
In September 2006, Procon installed an Ultraspin system to assist Total SA with the treatment of oily water wastes from heavy vehicle workshop & vehicle washing. Here are the details of this case study of a fuel depot:
Product: SE: Oily Water Systems
Industry: Oil Industry: Fuel Depot (Maintenance Workshops)
Client: Total South Africa
Location: Windhoek
Application: Treatment of oily water wastes from heavy vehicle workshop & vehicle washing. Oil is collected in an above ground tank with automatic drain back to the water collection pit.
Equipment Supplied: 0S35 (3.5 m 3/h unit)
Typical Process Data: Treated Water Flow up to 3.5m 3
Pump Feed Pressure: 300 to 400 kPa
Temperature: 5 to 25 ° C
Oil Type:
- Diesel
- Engine oil
- Lubrication oil
Design influent:
- Oil and grease (mg/l): 90 to 2500
- Suspended solids (mg/l) 1000 to 199
Design Effluent:
- Oil and grease (mg/l): <10 to < 50
- Suspended solids (mg/l): <100
Start up date: September, 2006
Discharge Source: Storm water
System Advantages:
- System performance easily within stormwater discharge limits
- Low operating and maintenance cost
- Performance improvements can be made
- Very small footprint compared to C.P.S
- Pressurised water and oil discharges

Contact Procon at our Witbank or Pretoria branch now!